Table 12 - Details of Inspection Results
Pole Condition Count Percent Insulator Condition Count Percent
0-Satisfactory 678 94.8% 0-Satisfactory 713 99.7%
1-Upper Pole Decay 16 2.2% 1-Contaminated, Residue 0 0.0%
2-Ground Line Decay 11 1.5% 2-Visible Crack 0 0.0%
3-Termite Damage 2 0.3% 3-Broken 0 0.0%
4-Slight Lean (< 15 deg) 27 3.8% 4-Leaning 0 0.0%
5-Severe Leaning (> 15 deg) 2 0.3% 5-Tie Unraveled 0 0.0%
6-Broken 0 0.0% 6-Pin Pull/Pushing Thru Arm 0 0.0%
7-Treated (Wrap, etc) 0 0.0% 7-Pin Broken 0 0.0%
8-C-Trussed 0 0.0% 8-Pin corroded 2 0.3%
9-Adjacent Pole (Old & Needs Removal) 1 0.1% 9-Other 0 0.0%
10-Other 7 1.0% 715 100.0%
X-Arm Type Count Percent X-Arm Condition Count Percent
0-Wooden (Single) 258 33.2% 0-Satisfactory 741 96.9%
1-Wooden (Double) 147 18.9% 1-Split 21 2.7%
2-Stand-Off-Metal 12 1.5% 2-Burnt/Rotted 2 0.3%
3-Stand-Off- Poly 1 0.1% 3-Termite Damage 1 0.1%
4-Stand-Off w/ Squirrel Guard 0 0.0% 4-No Braces (on X-arm) 0 0.0%
5-Alley Arm 2 0.3% 5-Failing @ Thru-Bolt 0 0.0%
6-None 353 45.4% 6-Broken 0 0.0%
7-Other - list 4 0.5% 7-Corroded 0 0.0%
777 100.0% 8-Other 0 0.0%
765 100.0%
Device Count Percent Device Condition Count Percent
0-None 332 24.8% 0-Satisfactory 985 97.5%
1-Fuse (Cut-Out) 353 26.4% 1-Corrosion, Rust, Pitting 14 1.4%
2-Arrestor 305 22.8% 2-Bushing Broken/Cracked 0 0.0%
3-XFMR 256 19.1% 3-Arrestor - Missing 0 0.0%
4-Capacitor-Fixed 1 0.1% 4-Arrestor - Obsolete 1 0.1%
5-Capacitor-Switched 2 0.1% 5-Arrestor - Long Lead 0 0.0%
6-Regulator (No.) 3 0.2% 6-Arrestor/Failed/Damaged 4 0.4%
7-Recloser/Sectionalizer 8 0.6% 7-Hardware Hanging 0 0.0%
8-Disconnects-Single Blade 0 0.0% 8-XFMR Disc'd (Needs Removal) 0 0.0%
9-3-Phase Tie Switch (Type) 77 5.8% 9-Riser Pothead/Connection Prob. 0 0.0%
10-Riser on Pole 0 0.0% 10-Riser w/o Ventilation 1 0.1%
11-Other - List 0 0.0% 11-Other 5 0.5%
1337 100.0% 1010 100.0%
Conductor Condition Count Percent Shield Wire Condition Count Percent
0-No Visible Problems 712 99.4% 0-Satisfactory 395 98.8%
1-Conductor Sag 2 0.3% 1-No Shield Wire 314 44.0%
2-Tight Phase Separation 0 0.0% 2-Shield Wire < 45 Degrees 0 0.0%
3-Poss Clearance Violation 1 0.1% 3-Shield Wire > 45 Degrees 1 0.3%
4-Clamps Worn/Loose 0 0.0% 4-Corrosion 4 1.0%
5-Ties Unraveled 0 0.0% 5-Broken Strands 0 0.0%
6-Pitted,Corrosion 1 0.1% 6-Other - List 0 0.0%
7-Strands Broken 0 0.0% 400 100.0%
8-Some Melting 0 0.0%
9-Guy, Other Contact 0 0.0% Guy/Anchor Condition Count Percent
10-Ground Wire Cut or Missing 0 0.0% 0-Satisfactory 261 83.1%
11-Other 0 0.0% 1-Guy Wire Strands Broken 3 1.0%
716 100.0% 2-Guy Rusted 22 7.0%
3-Anchor-Tight 0 0.0%
ROW Condition Count Percent 4-Anch - Loose or Broken 0 0.0%
0-Clear (No trees or Underbrush) 323 45.2% 5-Guy Missing or Deteriorated 0 0.0%
1-Trees/Limbs >8' 105 14.7% 6-Slack Span on Stub 0 0.0%
2-Trees/Limbs 3>d<8' 117 16.4% 7-Guard Defective/Missing 16 5.1%
3-Trees/Limbs < 3' 119 16.6% 8-Other 9 2.9%
4-Trees/Limb Contact 51 7.1%
5-Danger Tree 0 0.0% Attachments Count Percent
6-Underbrush w/in 3' 0 0.0% 1-Telephone 349 48.8%
7-Vines, Moderate 0 0.0% 2-CATV 390 54.5%
8-Vines, Severe 0 0.0% 3-Unknown 8 1.1%
9-Other 0 0.0% 4-Pole Extender 1 0.1%
5-Secondary 280 39.2%
6-Service 386 54.0%
7-Street Light/Spotlight 139 19.4%
8-Other 13 1.8%
715 100.0%