-76- This document, and the opinions, analysis, evaluations, or recommendations contained herein are for the sole use and benefit of the contracting parties.
There are no intended third party beneficiaries, and Jacobs Consultancy shall have no liability whatsoever to third parties for any defect, deficiency, error,
omission in any statement contained in or in any way related to this document or the services provided.
Table 12 - Details of Inspection Results
Pole Condition Count Percent Insulator Condition Count Percent
0-Satisfactory 828 96.3% 0-Satisfactory 855 99.2%
1-Upper Pole Decay 18 2.1% 1-Contaminated, Residue 1 0.1%
2-Ground Line Decay 10 1.2% 2-Visible Crack 0 0.0%
3-Termite Damage 1 0.1% 3-Broken 1 0.1%
4-Slight Lean (< 15 deg) 9 1.0% 4-Leaning 3 0.3%
5-Severe Leaning (> 15 deg) 3 0.3% 5-Tie Unraveled 1 0.1%
6-Broken 0 0.0% 6-Pin Pull/Pushing Thru Arm 0 0.0%
7-Treated (Wrap, etc) 0 0.0% 7-Pin Broken 0 0.0%
8-C-Trussed 0 0.0% 8-Pin corroded 1 0.1%
9-Adjacent Pole (Old & Needs Removal) 1 0.1% 9-Other 0 0.0%
10-Other 7 0.8% 862 100.0%
X-Arm Type Count Percent X-Arm Condition Count Percent
0-Wooden (Single) 377 39.5% 0-Satisfactory 922 98.7%
1-Wooden (Double) 171 17.9% 1-Split 5 0.5%
2-Stand-Off-Metal 75 7.9% 2-Burnt/Rotted 5 0.5%
3-Stand-Off- Poly 19 2.0% 3-Termite Damage 1 0.1%
4-Stand-Off w/ Squirrel Guard 0 0.0% 4-No Braces (on X-arm) 1 0.1%
5-Alley Arm 19 2.0% 5-Failing @ Thru-Bolt 0 0.0%
6-None 293 30.7% 6-Broken 0 0.0%
7-Other - list 1 0.1% 7-Corroded 0 0.0%
955 100.0% 8-Other 0 0.0%
934 100.0%
Device Count Percent Device Condition Count Percent
0-None 360 22.0% 0-Satisfactory 1261 99.4%
1-Fuse (Cut-Out) 393 24.0% 1-Corrosion, Rust, Pitting 0 0.0%
2-Arrestor 418 25.6% 2-Bushing Broken/Cracked 0 0.0%
3-XFMR 344 21.0% 3-Arrestor - Missing 0 0.0%
4-Capacitor-Fixed 10 0.6% 4-Arrestor - Obsolete 0 0.0%
5-Capacitor-Switched 7 0.4% 5-Arrestor - Long Lead 0 0.0%
6-Regulator (No.) 9 0.6% 6-Arrestor/Failed/Damaged 8 0.6%
7-Recloser/Sectionalizer 29 1.8% 7-Hardware Hanging 0 0.0%
8-Disconnects-Single Blade 1 0.1% 8-XFMR Disc'd (Needs Removal) 0 0.0%
9-3-Phase Tie Switch (Type) 62 3.8% 9-Riser Pothead/Connection Prob. 0 0.0%
10-Riser on Pole 2 0.1% 10-Riser w/o Ventilation 0 0.0%
11-Other - List 0 0.0% 11-Other 0 0.0%
1635 100.0% 1269 100.0%
Conductor Condition Count Percent Shield Wire Condition Count Percent
0-No Visible Problems 860 99.9% 0-Satisfactory 492 99.8%
1-Conductor Sag 0 0.0% 1-No Shield Wire 367 42.7%
2-Tight Phase Separation 0 0.0% 2-Shield Wire < 45 Degrees 0 0.0%
3-Poss Clearance Violation 1 0.1% 3-Shield Wire > 45 Degrees 1 0.1%
4-Clamps Worn/Loose 0 0.0% 4-Corrosion 0 0.0%
5-Ties Unraveled 0 0.0% 5-Broken Strands 0 0.0%
6-Pitted,Corrosion 0 0.0% 6-Other - List 0 0.0%
7-Strands Broken 0 0.0% 860 100.0%
8-Some Melting 0 0.0%
9-Guy, Other Contact 0 0.0% Guy/Anchor Condition Count Percent
10-Ground Wire Cut or Missing 0 0.0% 0-Satisfactory 245 75.6%
11-Other 0 0.0% 1-Guy Wire Strands Broken 0 0.0%
861 100.0% 2-Guy Rusted 67 20.7%
3-Anchor-Tight 0 0.0%
ROW Condition Count Percent 4-Anch - Loose or Broken 0 0.0%
0-Clear (No trees or Underbrush) 502 58.4% 5-Guy Missing or Deteriorated 0 0.0%
1-Trees/Limbs >8' 128 14.9% 6-Slack Span on Stub 0 0.0%
2-Trees/Limbs 3>d<8' 86 10.0% 7-Guard Defective/Missing 15 4.6%
3-Trees/Limbs < 3' 117 13.6% 8-Other 7 2.2%
4-Trees/Limb Contact 26 3.0%
5-Danger Tree 0 0.0% Attachments Count Percent
6-Underbrush w/in 3' 0 0.0% 1-Telephone 394 45.8%
7-Vines, Moderate 0 0.0% 2-CATV 459 53.4%
8-Vines, Severe 1 0.1% 3-Unknown 5 0.6%
9-Other 0 0.0% 4-Pole Extender 3 0.3%
5-Secondary 308 35.8%
6-Service 437 50.8%
7-Street Light/Spotlight 178 20.7%
8-Other 0 0.0%